Febco 825Y 1 1/4 Inch Reduced Pressure Zone Assembly w/Block Valves


Febco 825Y 1 1/4 Inch Reduced Pressure Zone Assembly

View larger image

CODE: 825-FBV

List price: $922.25
Our price: $484.95
You save: $437.30 (47%)
2 item(s)

 
Description
Reviews

Febco 825Y

Reduced Pressure Zone Assembly w/Block Valves

 

 

 

 

 

 

Size: ¾ " - 2" (20mm - 50mm)

The FEBCO Series 825Y Reduced Pressure Zone Assemblies are used to protect against high hazard (toxic) fluids in water services to industrial plants, hospitals, morgues, mortuaries, and chemical plants. They are also used in irrigation systems, boiler feed, water lines and other installations requiring maximum protection.

 

Features

• Ultimate mechanical protection of potable water, against hazards of cross-connection contamination.

• Meets all specifications of AWWA, ASSE, CSA and approved by the Foundation for Cross-connection Control and Hydraulic Research at the University of Southern California.

• Flow curve generated by the Foundation of Cross-Connection Control and Hydraulic Research at the University of Southern California.

• Modular relief valve for ease of maintenance.

• Simple Service procedures. All internal parts serviceable in line.

• Low head loss.

• Spring loaded "Y" type check valves.

• Internal relief valve pressure sensing passages.

• Replaceable seat rings on all sizes.

• End connection – NPT ANSI / ASME B1.20.1

 

Specifications

The reduced pressure zone assembly shall consist of two independently operating, spring loaded, "Y" pattern check valves and one hydraulically dependent differential relief valve. The assembly shall automatically reduce the pressure in the "zone" between the check valves to at least 5psi lower than inlet pressure. Should the differential between the upstream and the zone of the unit drop to 2psi, the differential relief valve shall open and maintain

the proper differential. Mainline valve body and caps including relief valve body and cover shall be bronze. Check valve moving member shall be center stem guided. All

hydraulic sensing passages shall be internally located within the mainline and relief valve bodies and relief valve cover. Diaphragm to seat area ratio shall be 10:1 minimum. Relief valve shall have a removable seat ring. Check valve

and relief valve components shall be constructed so they may be serviced without removing the valve body from the line. All seat discs shall be reversible. Shutoff valves and test cocks shall be full ported ball valves. The assembly shall be rated to 175psi (12.1 bar) working pressure and water temperature range from 32°F to 140°F (0ºC - 60ºC).

The assembly shall meet the requirements of ASSE Standard 1013; AWWA Standard Code C511; CSA Standard B64.4; and approved by the Foundation

for Cross-Connection Control and Hydraulic Hydraulic Research at the University of Southern California.

 

Operation

In a flow condition the check valves are open with the pressure between the checks, called the zone, being maintained at least 5.0psi lower than the inlet pressure and the relief valve is maintained closed. Should abnormal conditions arise under no flow or reversal of flow, the

differential relief valve will open and discharge to maintain the zone at least 2psi lower than the supply.

When normal flow resumes, the zone’s differential pressure will resume and the relief valve will close.

 

Typical Installation

Reduced pressure zone assemblies should be installed with minimum clearance of 12" (300mm) between relief valve discharge port and floor or grade. They must be installed where discharge will not be objectionable and can be positively drained away. They should be installed where easily accessible for testing and maintenance and must be protected from freezing. Thermal water expansion and/or water hammer downstream of the backflow preventer can cause excessive pressure. Excessive pressure situations should be eliminated to avoid possible damage to the system and assembly.

 

Refer to local codes for specific installation requirements. Some codes may prohibit vertical installation.

 

 

 

 

Helpful Tools

 

Adobe Required Febco 825Y Installation Instructions

  

 

Adobe Required Febco 825Y Specification Sheet

  

 

Adobe Required  Febco 825Y Maintenance Manual

  

 

Adobe Required  Febco 825Y Freeze Protection Instructions

  

 

Adobe Required  Febco 825Y Cross-Connection Control Handbook

 

 

 

 